Publication 1757-RN508A-EN-P - October 2003
ProcessLogix R500.1 Service Pack 1 7
16. Close the DOS window.
17. Restart the PC.
Problems Resolved in
R500.1 SP1
This section lists Server and Client problems resolved since R500.1.
Server
TIP
To confirm that the sysbld has successfully installed
the new SQL Server components, open the log file:
C:\Honeywell\server\setup\CreateSQLObjectEMS.txt.
The last line of the file should be a "MESSAGE:
Complete" statement. You can ignore any other error
messages in this log.
If the last line of the log is not the message complete
as shown below, then the update has not been
installed successfully. You will need to reboot the
machine and repeat this procedure.
Table 2 Server Problems Resolved in R500.1 SP1
ISR Subsystem Description
36585 Alarm/Event Presentation Page acknowledge may acknowledge partially obscured alarms and messages
42247 Alarm/Event Presentation The SOE summary display does not automatically update when new SOE events are logged.
40394 Alarm/Event Subsystem msg acks and confirms are not reported to an OPC client
40997
DR 1-HY4OD
Alarm/Event Subsystem Alarm replacement algorithm doesn't replace if all alarms are active
45755 Alarm Pager The com port Write timeout is not being set and could cause the WriteFile calls to block
forever
44586 Allen Bradley Backup server can fail to connect to an AB PLC via a Digi terminal server on failover
43744 Backbuild (bckbld) pntbld and bckbld for algo80 with 40 character names is not working correctly
40447 Bristol Babcock Bristol Babcock SOE does not contain timestamp (date only)
40999 Conf. Daemon (confd) Server allows points to be built via hsccli before being fully started.
45541 Conf. Daemon (confd) If a CM or SCM is uploaded to the monitor tab. the control level SCANCTRLLVL is reset to 0
(zero)
45700 Conf. Daemon (confd) Associated Display field is always blank on upload to Control Builder
40861 Diagnostic Capture Tool DCT cannot create a cab file
39226
DR 1-EBH6D
Display Subsystem Dsply task can be stuck in an unusual state preventing Station from properly starting up
41251 Display Subsystem History values on point detail display do not indicate alarm conditions